5.3 Storage
Permissible conditions at the place of storage:
Storage temperature: -40 ... +85 °C [-40 ... +185 °F]
Humidity: 45 ... 75 % relative humidity (no condensation)
WARNING!
Before storing the pressure sensor (following operation), remove any residual media. This
is of particular importance if the medium is hazardous to health, e.g. caustic, toxic, carcino-
genic, radioactive, etc.

6. Commissioning, operation

CAUTION!
Prior to commissioning, the pressure sensor must be subjected to a visual inspection.
Check the diaphragm for any visible damage, since this is a safety-relevant component.
Leaking fluid is indicative of damage.
Only use the pressure sensor if it is in perfect condition with respect to safety.
6.1 Making the mechanical connection
Required tool: Open-ended spanner (spanner width 27 or 41)
With flush process connections, remove the protection cap not until shortly
before mounting. During installation, ensure that the diaphragm is not damaged.
During mounting, make sure that the sealing faces at the pressure sensor
and the measuring point are clean and undamaged.
Only ever screw in, or unscrew, the instrument via the spanner flats. Never
use the case as a working surface.
The correct torque depends on the dimensions of the process connection
and the sealing used (form/material).
When screwing in, avoid any jamming of the threads.
For information on tapped holes and welding sockets, see Technical
Information IN 00.14 at www.wika.com.
WIKA operating instructions pressure transmitter, model P-3x
EN
max. 10 Nm