DUCTING TO HVAC SYSTEMS
8
CAUTION!
DO NOT CONNECT WITH A STATIC PRESSURE GREATER THAN OR EQUAL TO +0.5 WG.
CONTACT TECHNICAL SUPPORT AT (800) 533-7533 FOR ADDITIONAL DETAILS.
1. Ducting Considerations:
•
All flexible ducting connected to the Santa Fe Ultra120V should be UL listed.
•
A short piece of flexible ducting on all Santa Fe Ultra120V duct connections is recommended to reduce noise
and vibration transmitted to rigid ductwork in the structure.
•
Use a minimum 8" diameter round or equivalent rectangular duct for total duct lengths of up to 25'.
•
Use a minimum 10" diameter round or equivalent rectangular duct for longer lengths.
•
Grills or diffusers on the duct ends must not excessively restrict airflow.
•
Effective dehumidification may require that ducting be branched to isolated, stagnant air flow areas. When
ducting to two or three areas, use 8" or larger diameter branch ducting. When ducting to four or more areas,
use 6" or larger diameter branch ducting. Provisions must be made to provide airflow from supply locations
to the central return location. Proper air distribution is important to ensure even humidity control and heat
distribution throughout the structure.
•
DO NOT locate the return in a bathroom or a kitchen.
2. Decide Where To Place The Unit.
CAUTION! ALLOW FOR ENOUGH SPACING TO PROPERLY ROUTE THE RETURN AND
SUPPLY CONNECTION
3. Place Dehumidifier On The Floor.
CAUTION! INTERNAL STOPS LIMIT FEET HEIGHT. DO NOT TIGHTEN FEET BEYOND THE
RESISTANCE PROVIDED BY STOPS.
a. Attach leveling feet.
800.533.7533 | Santa-Fe-Products.com
b. Supply ducts can be installed on both sides of the
unit. In cases where only one of the two supply
ducts is USED, the 8" duct cover can be installed to
concentrate the air supply through one duct.
Ultra
Series
Supply
Santa Fe ULTRA120V Installation & Operation Instructions
Ultra Series
Supply with
Duct Cover
11