04: ECO enable/disable
Interface
05: ECO voltage range setting
Interface
06: Bypass enable/disable when UPS is OFF
Interface
07: Bypass voltage range setting
Interface
Segurança e harmonia
ININTERRUPTA
Setting
Parameter 3: Enable or disable ECO function.
You may choose the following two options:
ENA: ECO mode enable
DIS: ECO mode disable (default)
Setting
Parameter 2 & 3: Set the acceptable high voltage point and low voltage point for ECO
mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from +7V to
+24V of the nominal voltage. (Default: +12V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in parameter 3 is from -7V to
-24V of the nominal voltage. (Default: -12V)
Setting
Parameter 3: Enable or disable Bypass function.
You may choose the following two options:
ENA: Bypass enable
DIS: Bypass disable
Setting
Parameter 2 & 3: Set the acceptable high voltage point and acceptable low voltage
point for Bypass mode by pressing the Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from 230Vac to 264Vac.
(Default: 264Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3
3. Operations
PH 8010 | PH 8020 | PH 8030
Uninterruptible Power Supply
EN