Toshiba RAV-HM561UT-E Manual De Instalación página 60

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 23
2
Each time [
] [
] setting button is pushed,
indoor unit numbers in the group control
change cyclically. Select the indoor unit to
change settings for.
• The fan of the selected indoor unit runs and the
louvers start swinging. The indoor unit can be
confirmed for which to change settings.
3
Push OFF timer button to confirm the
selected indoor unit.
Code No.
Set data
4
Push the menu button to make Code No.
[
] flash. Change Code No. [
[
] setting button.
5
Push the menu button to make Set data
[
] flash. Change Set data [
with [
] [
] setting button.
6
Push OFF timer button to complete the set
up.
• To change other settings of the selected indoor
4
unit, repeat from Procedure
.
7
When all the settings have been completed,
push ON/OFF button to finish the settings.
(Return to the normal mode)
"
" flashes and then the display content
disappears and the air conditioner enters the
normal stop mode. (The remote controller is
unavailable while "
" is flashing.)
• To change settings of another indoor unit,
1
repeat from Procedure
.
117-EN
 Installing indoor unit on high
ceiling
When an indoor unit is installed on a ceiling higher than
the standard height, make the high ceiling setting for
fan speed adjustment.
Follow to the basic operation procedure
1
2
3
4
5
6
7
(
).
[5d]
• Specify
for the Code No. in Procedure
• Select the set data for Procedure
list of ceiling possible to be installed" table in this
manual.
Set data
Ceiling height
Standard
0000
(Factory default)
0001
High ceiling (1)
0003
High ceiling (3)
Remote controller-less setting
] with [
]
Change the high-ceiling setting with the DIP switch on
the P.C. board.
* Once the Set data has been changed, though it can
be freely set to "0001" or "0003", to reset it to "0000"
]
(factory default), it need changing using remote
controller (sold separately). After set data change,
an air conditioner is operated. After setting has been
completed, restart the air conditioner.
SW501-2
SW501-1
MCU
(IC501)
Set data
Ceiling height
SW501-1
Standard
0000
(Factory default)
0001
High ceiling (1)
0003
High ceiling (3)
To restore the factory defaults
To return the DIP switch settings to the factory defaults,
set SW501-1 and SW501-2 to OFF, connect a
separately sold wired remote controller, and then set
[5d]
the data of Code No.
to "0000".
– 59 –
 To secure better effect of
heating
When it is difficult to obtain satisfactory heating due to
installation place of the indoor unit or structure of the
room, the detection temperature of heating can be
raised. Also use a circulator or other machinery to
circulate heat air near the ceiling.
4
Follow to the basic operation procedure
.
1
2
3
(
5
from the "Height
[06]
• Specify
• For the set data in Procedure
of shift value of detection temperature to be set up
from the following table.
Set data
0000
0001
0002
0003
0004
0005
0006
 Filter sign setting
According to the installation condition, the filter sign
term (Notification of filter cleaning) can be changed.
Follow to the basic operation procedure
1
2
3
(
[01]
• Specify
• For the set data in Procedure
of filter sign term from the following table.
Set data
0000
0001
0002
0003
SW501-2
0004
OFF
OFF
• The filter sign may be unavailable depending on the
ON
OFF
remote controllers.
OFF
ON
 How to set up swing type
The swing type of the louver can be selected.
Follow to the basic operation procedure
1
2
(
• Specify
• Select the following data for the set data in
Procedure
4
5
6
7
).
4
for the Code No. in Procedure
.
5
, select the set data
Detection temperature shift value
• About "Dual swing"
No shift
"Dual" means that louvers 01 and 03 are directed
+1°C
and swing in one direction and louvers 02 and 04 are
directed and swing in the opposite direction.
+2°C
(Factory default)
(When louvers 01 and 03 are directed downward,
louvers 02 and 04 are directed horizontally.)
+3°C
+4°C
• About "Cycle swing"
The four louvers swing independently at respective
+5°C
timings.
+6°C
CAUTION
CAUTION
Do not set the swing set data to "0000".
(This setting may cause a failure of the louvers.)
 How to set up louver lock
4
5
6
7
).
(No swing)
4
for the Code No. in Procedure
.
5
A position of the individual louvers (four directions) can
, select the set data
be locked.
Filter sign term
Follow to the basic operation procedure
None
1
2
(
150 H
• Specify
in Procedure
2500 H
(Factory default)
• Select the following data for the set data in
Procedure
5000 H
10000 H
Set data
* When (4) or (5) is selected, dew drop may occur
during cooling mode.
• When the setting has been determined,
3
4
5
6
7
).
[F0]
4
for the Code No. in Procedure
.
5
.
Set data
Swing of louvers
Standard swing
0001
(Factory default)
0002
Dual swing
0003
Cycle swing
3
4
5
6
7
).
[F1]
[F2]
[F3]
[F4]
,
,
, or
for the Code No.
4
.
5
.
(1)
(2)
(3)
0001
0002
0003
(4)
(5)
0004
0005
lights up.