PROGRAMMING AND COMMISSIONING
Configuring the Output Module Mode
The output module is supplied configured as a Supervised Output
Module (factory default setting). To change the output to relay
mode (Form C - volt-free changeover contacts) requires a separate
programming operation using the Device Direct Command in AgileIQ
(See Radio Programming and Commissioning Manual - ref. D200-
306-00 for details.)
Starting with an un-commissioned module:
1) Remove it from the back box.
2) Ensure that the address is set to 00 (default setting).
3) Insert the batteries.
4) Select the Device Direct Command tab in AgileIQ.
5) Double click on the screen to reveal the list of options and follow
the instructions to configure the output module mode.
Note: Remove the batteries from the device afterwards if the system
commissioning operation is not about to be done.
It is recommended that the output module configuration is noted for
future reference on the module label after commissioning:
OUTPUT MODULE:
Supervised
Commissioning
1) Remove the module from the back box.
2) Ensure that the correct address has been set.
3) Insert the batteries.
4) Refit the module and replace the back box front cover.
To load network parameters into the RF module, it is necessary to link
the RF gateway and the RF module in a configuration operation using
the AgileIQ software tool. At commissioning time, with the RF network
devices powered on, the RF gateway will connect and program them
with network information as necessary.
The RF module then synchronises with its other associated devices
as the RF mesh network is created by the Gateway. (For further
information, see the Radio Programming and Commissioning
Manual - ref. D200-306-00.)
NOTE: Do not run more than one USB interface at a time to
commission devices in an area.
WIRING DIAGRAMS
Figure 6: Output Module Supervised
N200-309-00
Notifier by Honeywell, 140 Waterside Road, Hamilton Industrial Estate, Leicester, LE5 1TN, UK
Relay
¨
¨
Figure 7: Input / Output Module Relay Mode
0333 19
Notifier Fire Systems by Honeywell
Pittway Tecnologica S.r.l. Via Caboto 19/3
34147 TRIESTE, Italy
EN54-25: 2008 / AC: 2010 / AC: 2012
Components Using Radio Links
EN54-18: 2005 / AC: 2007 Input/Output Devices
for use in fire detection and fire alarm systems for buildings
EU Declaration of Conformity
Hereby, Notifier by Honeywell
declares
NRX-M711
is in compliance
The full text of the EU DoC can be requested from:
HSFREDDoC@honeywell.com
Patents Pending
DOP-IRF026
that the radio equipment type
with directive 2014/53/EU
I56-4294-002