BASIC INSTRUCTIONS
2. Connection Diagram
(Model CIMR-F7C47P5 shown below)
Main contactor
Fuses
L1
3-phase power
L2
380 to 480 V
50/60 Hz
L3
PE
Forward Run/Stop
Reverse Run/Stop
External fault
Fault reset
Multi-function
Multi-step speed setting 1
digital inputs
[Factory setting]
Multi-step speed setting 2
Jog frequency selection
2k Ω
DC reactor to improve input
power factor (optional)
Short-circuit bar
T
R/L1
S/L2
Line
Filter
T/L3
S1
S2
S3
S4
S5
S6
S7
SN
SC
SP
E(G)
RP
Analog input setting
adjustment
+V
Ω
2k
3
0 to 10V
A1
2
1
A2
4 to 20mA
P
P
AC
-V
R+
P
R-
MEMOBUS
communication
S+
RS-485/422
P
S-
IG
Braking resistor unit (optional)
U
X
1
2
B1
B2
U/T1
V/T2
W/T3
Varispeed F7
CIMR-F7C47P5
MA
MB
MC
M1
M2
M3
M4
M5
M6
24V
Shield
Shield
E(G)
terminal
terminal
Pulse train input [Default:
MP
Frequency reference input]
0 to 32kHz
AC
Analog input power supply
+15V, 20mA
FM
Analog input 1: Master
frequency reference
Ω
0 to +10V (20 k )
Multi-function analog input 2
[Default: Frequency bias
AM
Ω
4 to 20mA (250
)]
AC
0V
Analog input power supply
-15V, 20mA
Terminating
resistance
Twisted-pair
Shielded wires
P
Shielded wires
Varispeed F7
M
Fault contact output
250 VAC, 1A max.
30 VDC, 1A max.
Contact output 1
[Default : Running]
Multi-function digital
Contact output 2
output
[Default : Zero speed]
250 VAC, 1A max.
30 VDC, 1A max.
Contact output 3
[Default :
Frequency agree 1]
Pulse train output
0 to 32kHz (2.2 k )
Ω
[Default: Output frequency]
Adjustment,
20 k Ω
-
+
Multi-function analog output 1
FM
(-10 to +10V 2mA / 4 to 20mA)
[Default: Output frequency 0 to +10V]
Adjustment,
Ω
20 k
-
+
Multi-function analog output 2
AM
(-10 to +10V 2mA / 4 to 20mA)
[Default: Output current 0 to +10V]
5