5.2 Explanation of settings
Settings that are not self-explanatory are described briefly below. For further
information, please refer to the help files in the software configuration programs
(see Section 5.3).
Inverter frequency
Output frequency if no AC is present at the input.
Adjustability: 50 Hz; 60 Hz
Input frequency range
Input frequency range accepted by the MultiPlus. The MultiPlus synchronises within
this range with the AC input frequency. The output frequency is then equal to the
input frequency.
Adjustability: 45 – 65 Hz; 45 – 55 Hz; 55 – 65 Hz
Input voltage range
Voltage range accepted by the MultiPlus. The MultiPlus synchronises within this
range with the AC input voltage. The output voltage is then equal to the input
voltage.
Adjustability:
Lower limit: 180 - 230 V
Upper limit: 230 - 270 V
Inverter voltage
Output voltage of the MultiPlus in battery operation.
Adjustability: 210 – 245 V
Stand-alone / parallel operation / 2-3 phase setting
Using several devices, it is possible to:
increase total inverter power (several devices in parallel)
create a split-phase system
create a 3-phase system.
The standard product settings are for standalone operation. For parallel, three
phase
or split phase operation see section 4.6.6 and 4.6.7.
Search Mode (Applicable in stand-alone configuration only)
If search mode is "on", the power consumption in no-load operation is decreased
by
approx. 70 %. In this mode the Compact, when operating in inverter mode, is
switched off in case of no load or very low load, and switches on every two seconds
for a short period. If the output current exceeds a set level, the inverter will continue
to operate. If not, the inverter will shut down again.
The Search Mode can be set with a DIP switch.
The Search Mode "shut down" and "remain on" load levels can be set with
VEConfigure.
The standard settings are:
Shut down: 40 Watt (linear load)
Turn on: 100 Watt (linear load)
15