IV.7 Datalogging of Current Waveform
When users see the above display and press the REC button, current waveform will be logged.
NOTE: Users can specify how many points per cycle to be logged in the
WAVEFORM CONFIGURATION of SETUP.
V. data logging of transient detection
When users move the sliding switch to the Transient position, the following display is shown.
It shows the reference voltage is AC 110.0V (TRANS REF), and the threshold is 5%. If the
voltage exceeds 115.5V (SWELL) or is less than 104.5V (DIP), or is less the 40.0V (OUTAGE),
one transient event will be logged.
NOTE: Maximum 32000 events