3.2 Select Installation Location
Never attempt! Improper operation may result in death or serious injury.
Be sure to observe! Improper operation may lead to personal injury or property damage.
Select a location which is strong
enough to hold unit's weight so that
unit can stand still and erect.
Please keep the unit away from
inflammable, explosive and
corrosive gas or waste gas.
Outdoor unit and indoor unit should
stay as close as possible to shorten
the length of refrigerant pipe and
reduce bend angles.
If the outdoor unit is totally surrounded by walls, please refer to the following figures for space dimension:
3.3 Piping Work Requirements
Height difference between outdoor unit should be 0m. Please refer to the table below for piping work
requirements:
Outer diameter (mm/inch)
R410A Refrigerant System
Φ6.35(1/4)
Φ9.52(3/8)
Φ12.70(1/2)
Φ15.9(5/8)
Φ19.05(3/4)
Make sure the unit is not exposed to sun
and rain. And the location can resist dust,
typhoon and earthquake.
Make sure the location has space for
heat exchange and maintenance so that
unit can operate reliably with good
ventilation.
Select a location which is out of children's
reach. Keep the unit away from children.
Fig.2
5
Wall thickness (mm)
≥0.8
≥0.8
≥0.8
≥1.0
≥1.0