(2) Selection of circuit breaker and power cord:
Model
AQ OUT HY 40
AQ OUT HY 45
AQ OUT HY 54
NOTES!
① Selection of circuit breaker and power cord in the above table is based upon unit's maximum power
(maximum current). Power cord should be wire of H05RN-F or above.
② Specification of power cord is based on the working condition where ambient temperature is 40℃
and multi-core copper cable (working temperature is 90℃, e.g. power cable with YJV cross-linked
copper, insulated PE and PVC sheath) is lying on the surface of slot. If working condition changes,
please adjust the specification according to national standard.
③ Specification of circuit breaker is based on the working condition where ambient temperature of
circuit breaker is 40℃. If working condition changes, please adjust the specification according to
national standard.
5 Check Items after Installation and Test Operation
5.1 Check Items after Installation
Check items
Each part of the unit is installed securely?
Gas leakage test is taken or not?
Unit gets proper thermal insulation or not?
Drainage is smooth or not?
Is the voltage in accordance with the rated voltage
specified on the nameplate?
Is the electric wiring and pipe connection installed
correctly?
Unit is securely grounded or not?
Power cord meets the required specification?
Is the air inlet/outlet blocked?
Length of refrigerant pipe and the charging amount
of refrigerant are recorded or not?
Whether the fixing loop at the foot of compressor for
transportation is removed?
5.2 Test Run
NOTES!
① When the unit is installed for the first time and main board of outdoor unit is replaced, please conduct
test run. Otherwise, the unit can't operate.
② Test run must be conducted by professional person or under the guidance of professional person.
Circuit breaker
Power
capacity (A)
220V~ 50HZ
220V~ 50HZ
220V~ 50HZ
Number of ground
wire×Min sectional area
32
32
40
Possible conditions due to improper
installation
Unit may drop, shake or emit noise
Insufficient cooling (heating) capacity
There may be condensate water.
There may be condensate water.
Unit may have malfunction or components
may get damaged.
Unit may have malfunction or components
may get damaged.
Electrical leakage
Unit may have malfunction or components
may get damaged.
Insufficient cooling (heating) capacity
The refrigerant charging amount is not
accurate.
It may damage the compressor.
22
Number of power cord×Min
sectional area (mm
2
(mm
)
1×4.0
1×4.0
1×6.0
2
)
2×4.0
2×4.0
2×6.0
Check record