Operation and Maintenance Documentation of air curtains GUARD PRO v202301
Settings menu
When Panel Intelligent is switched off, press and hold MODE for 5 seconds
To change option use MODE button.
To change value use +/- buttons.
Setting menu
1
2
3
4
5
6
7
8
9
10
11
Button lock / unlock
To LOCK buttons press and hold + and then – and hold both of them for 5 seconds.
To UNLOCK buttons press and hold + and then – and hold both of them for 5 seconds.
Press MODE
Change on manual mode
Hold MODE for 5 seconds
Change to cool mode
, heating mode
Press FAN
Change of the fan speed low
Hold FAN for 5 seconds
Manual callendar programming Monday – Friday, Saturday, Sunday 6 settings per day
BMS Functions
Setting/Reading work parameters
Work/Stop conditions
Weekly program
Temperature
Fan speed
Heating, ventilation, cool mode
Antifreeze mode
No.
Setting
1
Working Mode
2
Interface
3
Baud Rate
4
Byte
5
Modbus
6
Transmittion
7
Thermostat address
WIFI functions
Setting/Reading work parameters
Work/Stop conditions
Weekly program
Temperature
Fan speed
Heating, ventilation, cool mode
Option
Temperature calibration
EEPROM
Fan status
Temperature sensor
Antifreeze
Antifreeze range
ALARM
Drycontact
MODBUS
BMS speed
Modbus ID
or automatic mode
, ventilation
, medium
, high
, automatyczna
RS485 Semi-duplex; PC or main controller is master; thermostat is slave
RTU (Remote Terminal Unit) format (please refer to MOBUS instruction)
1-247;(0 is broadcast address and stand for all thermostat without response)
Value
–9°C ~ +9°C
0:no memory
1: memory
C1: Thermostatic mode
C2: Continuous mode
0: Internal Sensor
1: External Sensor NTC (optional)
0: Off
1: On
+5°C ~ +15°C
0: disable
1: enable
0: NO
1: NC
0: disable
1: enable
0-2400 / 1-9600 / 2-19200
1~247 (01~F7)
Paremeters
A(+),B(-), 2 wires
0-2400 / 1-9600 / 2-19200
9 bits in total: 8 data bit + 1 stop bit
RTU Mode