10. FIELD SETTING
• Confirm that all the installation work is complete for the indoor and outdoor units and the UV streamer air
purifier unit.
• Confirm that the control box lid of the indoor unit, outer panel of the outdoor unit, wiring cover and the
control box lid of the UV streamer air purifier unit are closed.
<Perform field setting from the remote controller after turning on the power supply.>
•
in the table indicates factory-default setting.
• Set up by switching 3 items: "Mode No.", "FIRST CODE No." and "SECOND CODE No.".
• The setting procedure and operating instructions are described in the installation manual supplied with
the remote controller.
(Note) The "Mode No." setting applies to the entire group; to set up or check the settings of an individual
indoor unit, specify the Mode No. in parentheses.
• Do not set other values than those indicated in the table.
Airflow rate setting
• Set the airflow rate.
MODEL GROUP
FCAG35
FXFQ20/25/32
FXFA20/25/32
FCAG71
FXFQ40
FXFA40
FCAG50/60/100/125/140
FCAHG100/125/140
FXFQ50/63/80/100/125
FXFA50/63/80/100/125
FCAHG71
Airflow rate setting when thermostat is OFF
• When cool/heating thermostat is OFF, in some models, the fan operates in "light breeze (LL airflow rate)"
mode (not displayed on the remote controller) to prevent drafts, etc.
If it is expected for the thermostat to turn OFF frequently, purification performance can be maintained by
operating with the airflow rate set on the remote controller when the thermostat is OFF.
Follow the installation manual of the indoor unit to set the air volume when thermostat control is OFF.
• Set up after explaining the details of the settings to the customer and obtaining their consent.
When changing the airflow rate, the airflow rate to be set must be explained to the customer.
19
01_EN_3P701968-3.indd 19
01_EN_3P701968-3.indd 19
Mode No.
FIRST CODE No.
(Refer to Note.)
13(23)
13(23)
13(23)
13(23)
13(23)
SECOND CODE No.
0
0
0
1
0
1
0
1
02
03
02
02
03
02
03
03
English
12/05/2023 15:12:34
12/05/2023 15:12:34