11. TRIAL OPERATION
<Check all items of "(1) Items to be checked after completion of work" on the front page.>
1. Perform trial operation in accordance with the installation manual supplied with the indoor unit.
• The UV streamer air purifier unit purifies air while the indoor unit is operating.
• Check the wired remote controller display (or the indicator of the decoration panel in the case of
wireless remote controller) to confirm that the UV streamer air purifier unit is operating normally.
(See the air cleaning/purification icon and error indicator on the display of the wired remote controller).
It is not possible to see the air cleaning/purification icon on the wireless remote controller display
(only errors are indicated on the receiver on the decoration panel).
For details, follow the installation and operation manual of the wired or wireless remote controller.
• Hissing and crackling noises while the UV streamer air purifier unit is operating are normal.
Error code AH: Air purifier (dust collection and purification) unit in error; for
CAUTION
If an error displays, carry out an inspection in accordance with the operation
manuals of the UV streamer air purifier unit and wired or wireless remote controller.
<Corner cover with operation display (5)>
Indicator
During normal operation : Blue (Lit)
Error in streamer unit : Blue (Blinking)
Error in UV unit : Red (Blinking)
Notification of streamer unit and UV unit replacement time : Red (Lit)
Unit operation is OFF: LED OFF
21
01_EN_3P701968-3.indd 21
01_EN_3P701968-3.indd 21
other error codes, refer to the installation manual supplied with
the indoor unit.
CAUTION
If an error is indicated, carry out an inspection
in accordance with the operation manual.