Vortice VORT HRI Manual De Instrucciones página 33

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 79
ENGLISH
Installer "Operations menu" page
Enter the password as shown in the figure to access the installer "Operations menu."
MAIN MENU
USE MENU
ALARM
SETUP
INFO
From this new page you can manage:
• Setp Byp.
"By-pass" function activation depends on the "Setp Byp"
temperature. "Setp Byp" is selectable into a variable range
between: 15°C & 30°C (default value = 18°C).
• Lifetime
Is shown the duration of Filters Pre-Alarm.
(See "Pre -alarm: Filters checking"):
- after 3 or 6 or 12 months;
• Reset Fil
In case of Filters replacing, you need to reset the Filters Timer
manually:
- select [YES] to reset;
- select [NO] to not resect.
• Modbus ID
In the presence of another HMI user interface installed in
remote, you can configure an address other than that set by
default which is "160" (for code 12106) or "1" (for code
12107). (page 39)
• Speed
See Fig. 3
From "Installer menu" page, selecting "Speed", you can join to
"Setting speed". Here, you can set motorfan speeds:
(C) Clean air outlet inside the room;
(D) Stale air outlet to outside.
For more details on setting "Speed", See:
"Setting Speed Menu"
All manuals and user guides at all-guidesbox.com
PASSWORD
023
TECHNIC.
SETP BYP.
LIFE TIME
RESET FIL
MBUS ID
SPEED
LANGUAGE
NO FROST
QUIET
QUIET PR.
SETP BYP.
018
LIFE TIME
003
RESET FIL
YES
MODBUS ID
160
SPEED
VSUP1
Å
VEXH1
VSUP2
VEXH2
VSUP3
VEXH3
VSUP B
VEXH B
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
[ ▲ ]
33