09: Programmable outlets setting
Interface
EN
10: Backup time setting for outlets
Interface
00: Exit setting
3-6. Operating Mode Description
Operating mode
Online mode
ECO mode
Frequency
Converter mode
Battery mode
Setting
Parameter 3: Set up backup time limits for
programmable outlets.
0-999: setting the backup time limits in minutes from
0-999 for programmable outlets which connect to
non-critical devices on battery mode.
Setting
Parameter 3: Set up backup time on battery mode for
general outlets.
0-999: setting the backup time in minutes from 0-999
for general outlets on battery mode.
0: When setting as "0", the backup time will be only 10
seconds.
999: When setting as "999", the backup time setting will
be disabled.
Description
When the input voltage is within
acceptable range, UPS will provide pure
and stable AC power to output. The UPS
will also charge the battery at online
mode.
Energy saving mode:
When the input voltage is within voltage
regulation range, UPS will bypass
voltage to output for energy saving.
When input frequency is within 40 Hz to
70 Hz, the UPS can be set at a constant
output frequency, 50 Hz or 60 Hz. The
UPS will still charge battery under this
mode.
When the input voltage is beyond the
acceptable range or power failure and
alarm is sounding every 4 second, UPS
will backup power from battery.
LCD display
13