2-2. Setup the UPS
Step 1: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension
cords.
 For 200/208/220/230/240VAC models: The power cord is supplied in the UPS package.
 For 100/110/115/120/127VAC models: The power cord is attached to the UPS. The input
EN
plug is a NEMA 5-15P for 1000, 1000L, 1500 and 1500L models, NEMA 5-20P for 2000 and
2000L models.
For Low voltage models
Note:
will be illuminated when the UPS is plugged into an improperly wired utility power outlet (Refer
to Troubleshooting section). Please also install a circuit breaker (40A) between the mains and
AC input in 3K model for safety operation.
Step 2: UPS output connection
For socket-type outputs, there two kinds of outputs: programmable outlets and general
outlets. Please connect non-critical devices to the programmable outlets and critical
devices to the general outlets. During power failure, you may extend the backup time to
critical devices by setting shorter backup time for non-critical devices.
For terminal-type input or outputs, please follow below steps for the wiring configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm
3.3mm
c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
Step 3: Communication connection
Communication port:
USB port
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the communication
port of your PC. With the monitoring software installed, you can schedule UPS
shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When
installing either SNMP or AS400 card in the UPS, it will provide advanced communication and
monitoring options.
PS. USB port and RS-232 port can't work at the same time.
Step 4: Network connection
Network/Fax/Phone surge port
Connect a single modem/phone/fax line into surge-protected "IN" outlet on the back panel of
the UPS unit. Connect from "OUT" outlet to the equipment with another modem/fax/phone line
cable.
: Check if the site wiring fault indicator lights up in LCD panel. It
2
2
-5.3mm
power cords for NEMA type.
RS-232 port
2
power cords. Suggest using WG12-10 or
Intelligent slot
5