WIRING DIAGRAMS
The connections to be carried out by the installer are:
- Main supply line
- Thermostatic line
- Any flame modulation thermostat to terminals L1-N1 of plug G and bridge N1 must be removed from such plug. Tmf only
works with the min./max. switch turned to max.
Legend
BRM Motor relay coil
CRM Motor relay contacts
CRT
Thermal relay contact
EC
Control electrode
F
Fuse
FA
Anti-interference filter
IG
Main switch
Ima
ON/OFF switch
NOTE: Always make sure that no more than two wires are connected to each terminal.
Warning:
- Do not invert the neutral with the phase.
- Make the connection to an efficient earthing system.
- The electrical power line to the burner must be fitted with an omnipolar switch with an opening of at least 3 mm between
the contacts.
- The earth connection to the terminal board of the burner must be made with a cable at least 20 mm longer than the phase
and neutral cables.
- Must be workmanlike performed and comply with the local regulations in force.
I.m.M. Min./max. switch
MB
Burner motor
MR
Auxiliary terminal board
MS
Servocontrol terminal board
MPE Control box terminal board
PA
Air pressure switch
PGm Minimum gas pressure switch
RT
Thermal relay
- 30
-
Mains supply
230/400 V - 50 Hz
TC
Boiler thermostat
Tmf
2nd stage modulation thermo-
stat (if present)
TP
Timer
TR
Ignition transformer
VP
Main safety valve
VS
2nd safety valve (if present)