Transmission cable specifications
Type of cable
Cable diameter
Maximum length of transmission lines for centralized control and indoor/
outdoor transmission lines (Maximum length via indoor units):
Remarks
The maximum length of the wiring between power supply unit for
transmission lines (on the transmission lines for centralized control) and
each outdoor unit and system controller is 200 m [656 ft].
*1 Connected with simple remote controller.
9.1. Power supply wiring
Use dedicated power supplies for the indoor unit.
Bear in mind ambient conditions (ambient temperature, direct sunlight, rain water, etc.) when proceeding with the wiring and connections.
The wire size is the minimum value for metal conduit wiring. If the voltage drops, use a wire that is one rank thicker in diameter. Make sure the power-supply voltage
does not drop more than 10%.
�����������������������������������������
Power supply cords of appliances shall not be lighter than design 245 IEC 57, 227 IEC 57, 245 IEC 53 or 227 IEC 53.
A switch with at least 3 mm [1/8 in] contact separation in each pole shall be provided by the Air conditioner installation.
[Fig. 9.1.1] (P.5)
A Ground-fault interrupter
B Local switch/Wiring breaker
C Indoor unit
D Pull box
Total operating current of the
Indoor unit
Main cable
F0 = 16 A or less
*2
F0 = 25 A or less
*2
F0 = 32 A or less
*2
Apply to IEC61000-3-3 about Max. Permissive System Impedance.
*1 The Ground-fault interrupter should support Inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
*2 Please take the larger of F1 or F2 as the value for F0.
F1 = Total operating maximum current of the indoor units × 1.2
F2 = {V1 × (Quantity of Type1)/C} + {V1 × (Quantity of Type2)/C} + {V1 × (Quantity of Type3)/C} + {V1 × (Quantity of Others)/C}
Indoor unit
Type1
TPEFYP***MS140C
Type2
TPEFYP***MA143A, TPVFYP***AM140(1)A
Type3
TPEFYP***MH140A
Type4
TPCFYP***KM140B
TPKFYP***HM142A, TPKFYP***KM142A,
Type5
TPMFYP***BM140E
Type6
TPLFYP***EM140(1)A, TPLFYP***FM140A
Others
Other indoor unit
C : Multiple of tripping current at tripping time 0.01s
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
*Condition TPEFYP***MS140C × 4 + TPEFYP***MA143A × 1, C = 8 (refer to right sample chart)
F2 = 18.6 × 4/8 + 38 × 1/8
= 14.05
→ 16 A breaker (Tripping current = 8 × 16 A at 0.01s)
*3 Current sensitivity is calculated using the following formula.
G1 = (V2 × Quantity of Type1) + (V2 × Quantity of Type2) + (V2 × Quantity of Type3) + (V2 × Quantity of Others) + (V3 × Wire length [km])
G1
Current sensitivity
30 or less
30 mA 0.1 sec or less
100 or less
100 mA 0.1 sec or less
12
Transmission cables
Shielding wire (2-core)
CVVS, CPEVS or MVVS
More than 1.25 mm
2
[AWG 16]
Max length: 200 m [656 ft]
500 m [1640 ft] MAX
Minimum wire thickness (mm
)
2
Branch
Ground
1.5
1.5
1.5
2.5
2.5
2.5
4.0
4.0
4.0
Wire thickness
ME Remote controller cables
Sheathed 2-core cable (unshielded) CVV
0.3 ~ 1.25 mm
[AWG 22 ~ 16]
2
(0.75 ~ 1.25 mm
2
[AWG 18 ~ 16])*1
When 10 m [32 ft] is exceeded, use
�����������������
as transmission cables.
CVVS, MVVS: PVC insulated PVC jacketed shielded control cable
CPEVS: PE insulated PVC jacketed shielded communication cable
CVV: PVC insulated PVC sheathed control cable
Local switch (A)
Ground-fault interrupter
*1
Capacity
20 A current sensitivity
*3
16
30 A current sensitivity
*3
25
40 A current sensitivity
32
*3
V1
V2
18.6
2.4
38
1.6
13.8
4.8
19.8
2.4
9.9
2.4
17.1
2.4
0
0
V3
1.5 mm
2
48
2.5 mm
56
2
4.0 mm
2
66
MA Remote controller cables
0.3 ~ 1.25 mm
[AWG 22 ~ 16]
2
(0.75 ~ 1.25 mm
2
[AWG 18 ~ 16])*1
Max length: 200 m [656 ft]
Breaker for wiring (A)
(Non-fuse breaker)
Fuse
16
20
25
30
32
40
Rated Tripping current (x)