5. Installing the unit
5.1. Hanging the unit body
u Bring the indoor unit to an installation site as it is packed.
u To hang the indoor unit, use a lifting machine to lift and pass through
the hanging bolts.
u Install the indoor unit before ceiling joint construction.
[Fig. 5.1.1] (P.2)
A Unit body
B Lifting machine
[Fig. 5.1.2] (P.2)
C ���������
D Washers
E ���������������
6. Refrigerant pipe and drain pipe specifications
To avoid dew drops, provide ����� antisweating and insulating work to the
refrigerant and drain pipes.
When using commercially available refrigerant pipes, be sure to wind commer-
cially available insulating material (with a heat-resisting temperature of more
than 100°C [212°F] and thickness given below) onto both liquid and gas pipes.
Be also sure to wind commercially available insulating material (with a form
polyethylene's ���� gravity of 0.03 and thickness given below) onto all pipes
which pass through rooms.
1 Select the thickness of insulating material by pipe size.
Pipe size
6.4 mm to 25.4 mm [1/4 in to 1 in]
28.6 mm to 38.1 mm [1-1/8 in to 1-1/2 in]
2 If the unit is used on the highest story of a building and under conditions of
high temperature and humidity, it is necessary to use pipe size and insulating
material's thickness more than those given in the table above.
3 If there are customer'������������������
6.1. Refrigerant pipe specifications
Refrigerant pipe sizes
Model
Item
Liquid pipe
Refrigerant pipe
(Brazing connection)
Gas pipe
6.2. Refrigerant pipe, drain pipe and filling
port
[Fig. 6.2.1] (P.2)
A Air inlet
C Refrigerant piping (gas)
E Drain outlet
Insulating material's thickness
More than 10 mm [7/16 in]
More than 15 mm [5/8 in]
TPEFYP***MH142A
015·018
024·027·030·036·048·054
ø 6.35 mm
ø 9.52 mm
[1/4 in]
[3/8 in]
ø 12.7 mm
ø 15.88 mm
[1/2 in]
[5/8 in]
B Refrigerant piping (liquid)
D Control box
F Air outlet
5.2. Confirming the unit's position and fix-
ing hanging bolts
u Ensure that the hanging bolt nuts are tightened to fix the hanging bolts.
u To ensure that drain is discharged, be sure to hang the unit at level us-
ing a level.
Caution:
Install the unit in horizontal position. If the side with drain port is installed
higher, water leakage may be caused.
9