Furnace Fan (G) ON
HiSpeed Fan (Y) ON
Furnace Fan (G) OFF
HiSpeed Fan (Y) OFF
HiSpeed Fan Stage 1 (Y1) ON
HiSpeed Fan Stage 2 (Y2) ON
HiSpeed Fan Stage 1 (Y1) OFF
HiSpeed Fan Stage 2 (Y2) OFF
Furnace Fan (G) ON
HiSpeed Fan (Y) ON
Furnace Fan (G) OFF
HiSpeed Fan (Y) OFF
*For more details about the dry mode process, please refer to the Outdoor Unit Manual
HiSpeed Fan Stage 1 (Y1) ON
HiSpeed Fan Stage 2 (Y2) ON
HiSpeed Fan Stage 1 (Y1) OFF
HiSpeed Fan Stage 2 (Y2) OFF
*For more details about the dry mode process, please refer to the Outdoor Unit Manual
Specifications are subject to change without notice.
PAA-A18, 24, 30, 36, 42AA1/BA1/CA1 and all-
Cool Mode - Single Speed Fan
(TRA - TO ≥ 0.9 °F [0.5 °C])
(TRA - TO < 0.9 °F [0.5 °C]) AND Mode 27 = 2
(TRA - TO < 0.9 °F [0.5 °C])
Cool Mode - Dual Speed Fan
(TRA - TO ≥ 0.9 °F [0.5 °C])
(TRA - TO ≥ 0.9 °F [0.5 °C]) AND FanSpeed = High OR
(TRA - TO ≥ 3.6 °F [2.0 °C]) AND FanSpeed = Auto
(TRA - TO < 0.9 °F [0.5 °C]) AND Mode 27 = 2
(TRA - TO < 0.9 °F [0.5 °C])
Dry Mode - Single Speed Fan
(TRA - TO ≥ 0.9 °F [0.5 °C])
Inactive during Dry mode
(TRA < 64.4 °F [18 °C])
Inactive during Dry mode
Dry Mode - Dual Speed Fan
(TRA - TO ≥ 0.9 °F [0.5 °C])
Inactive during Dry mode
(TRA < 64.4 °F [18 °C])
Inactive during Dry mode