 2st stage fan air gate valve
Set switch 2) (Fig. 22 pag. 21) to the 2nd stage position and ad-
just the air gate valve 6)(Fig. 24) by turning the hex element
4)(Fig. 24), after having loosened the ring nut 3)(Fig. 24).
Air pressure at connection 1)(Fig. 25) must be approximately the
same as the pressure specified in the table (Fig. 25) plus the
combustion chamber pressure measured at connection 2). Refer
to the example in the adjacent figure.
TL
TR
0
LED
RMO
*
6069
Burner calibration
A
A
*
Off
Yellow
For further details see pag. 26.
RL 70
kg/h
mbar
40
8.5
50
8.6
60
8.8
70
9.2
mbar = air pressure in 1) with zero pressure in 2)
With shutter 4) retracted (Fig. 8 pag. 12)
(1)
NOTE:
in order to facilitate adjustment of hex elements 2) and
4)(Fig. 24), use a 3 mm Allen key 5) (Fig. 24).
TL
LED
RMO
*
D3280
Green
22
GB
RL 100
RL 130
kg/h
mbar
kg/h
60
7.2
80
70
7.7
90
80
8.4
100
90
9.3
110
100
11.0
120
130
130
D700
Red
mbar
7
7.2
7.6
8.1
9.0
11.0
8.5
(1)
Tab. E
Fig. 25
D3281
Fig. 26