Descargar Imprimir esta página

Siemens SIMATIC S7-300 Información Del Producto página 14

Ocultar thumbs Ver también para SIMATIC S7-300:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 28
Supplement: UKEX approval
According to EN IEC 60079-7 +A1 (Explosive atmospheres - Part 7: Equipment protection by increased safety "e"), EN IEC
60079-15 (Explosive atmospheres - Part 15: Equipment protection by type of protection "n") und EN IEC 60079-0 (Explosive
atmospheres - Part 0: Equipment - General requirements).
II 3 G Ex ec nC IIC Tx Gc
DEKRA 21UKEX0011 X
Special conditions in explosive atmospheres
The equipment shall only be used in an area of not more than pollution degree 2, as defined in EN 60664-1.
The equipment must be installed in a suitable enclosure providing a degree of protection not less than IP54 in accordance
with EN IEC 60079-0 and EN 60529. The ambient conditions must be taken into consideration for use.
Provisions shall be made to prevent the nominal voltage from being exceeded by transient disturbances of more than
119 V.
The following applies to SM 326; DI 8 x NAMUR:
According to EN IEC 60079-7 +A1 (Explosive atmospheres - Part 7: Equipment protection by increased safety "e"), EN IEC
60079-11 (Explosive atmospheres - Part 11: Equipment protection by intrinsic safety "i") und EN IEC 60079-0 (Explosive
atmospheres - Part 0: Equipment - General requirements).
II 3 G (2) G Ex ec [ib Gb] IIC T4 Gc
II 3 G (2) D Ex ec [ib IIIC Db] IIC T4 Gc
Special conditions apply to SM 326; DI 8 x NAMUR in hazardous areas:
During installation the connection box shall be used, or by using a separation wall a minimum distance of 50 mm shall be
guaranteed between the intrinsically safe and non-intrinsically safe circuits, or the connection parts shall be additionally
insulated (e.g. by heat-shrinkable tubing).
When installed in an area requiring EPL Ge, the following additionally apply:
The equipment shall only be used in an area of not more than pollution degree 2, as defined in EN 60664-1.
The equipment shall be installed in a suitable enclosure that provides a degree of protection not less than IP54 in
accordance with IEC 60079-0 and EN 60529. The ambient conditions must be taken into consideration for use.
Provisions shall be made to prevent the nominal voltage from being exceeded by transient disturbances of more than
119 V.
Supplement: CCCEx approval
In accordance with GB/T 3836.3 (Explosive atmospheres - Part 3: Equipment protection by increased safety "e"), GB/T 3836.8
(Explosive atmospheres - Part 8: Equipment protection by type of protection "n") und GB/T 3836.1 (Explosive atmospheres -
Part 1: Equipment - General requirements).
Ex ec nC IIC Tx Gc
Special conditions in hazardous areas:
The equipment shall only be used in an area of not more than pollution degree 2, as defined in GB/T 16935.1.
The equipment shall be installed in a suitable enclosure providing a degree of protection not less than IP54 in accordance
with GB/T 3836.1 and GB/T 4208. The ambient conditions must be taken into consideration for use.
Provisions shall be made to prevent the nominal voltage from being exceeded by transient disturbances of more than
119 V.
The following applies to SM 326; DI 8 x NAMUR:
In accordance with GB/T 3836.3 (Explosive atmospheres - Part 3: Equipment protection by increased safety "e"), GB/T 3836.4
(Explosive atmospheres - Part 4: Equipment protection by intrinsic safety "i") and GB/T 3836.1 (Explosive atmospheres - Part
1: Equipment - General requirements).
Ex ec [ib Gb] IIC T4 Gc
Ex ec [ib IIIC Db] IIC T4 Gc
14
Product information on fail-safe signal modules
A5E50592408-AA, 11/2022

Publicidad

loading

Este manual también es adecuado para:

Simatic et 200m