Descargar Imprimir esta página

Hitachi PSC-5S Manual De Instalación Y Funcionamiento página 11

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 27
2. Selection of Indoor Unit To Be Set:
Change Ref. No. by depressing " " (TEMP) switch and I.U. Add. by " " (TEMP) switch, and select
the indoor unit to be set. The indication is changed in order as shown below.
00
ATTENTION:
- When the indication of Ref. No. is "- -", the indication of I.U. Add. is also "- -". In such a case,
I.U. Add. can not be changed although the " " (TEMP) switch is depressed.
- Ref. No. with no indoor unit connected and I.U. Add. not connected are not indicated.
- The indoor unit already set as the master unit is not indicated.
Ref. No.: Select
by depressing " "
(TEMP) switch.
(ex. When selecting indoor unit of Ref. No. 4 and
I.U. Add. 9)
3. Setting Procedure:
Depress the "RUN/STOP" switch after selecting indoor unit, the indicated unit is set as the master
unit, and the " " and "SET" indications appear.
(Every time the "RUN/STOP" switch is depressed, the master unit is set and canceled
alternately.)
" " and "SET" Indications: ON
CAUTION:
- Only one indoor unit can be set as the master unit in one group. Other indoor unit can not be
set as the master unit for the group with the master unit set already. For setting the master
unit as the master unit for another group, cancel the present master unit setting and perform
the setting for another group.
- In case that there are indoor units with auto-louver and indoor units without auto-louver in the
same group, set the indoor unit with auto-louver as the master unit. If the indoor unit without
auto-louver is set as the master unit, the auto-louver setting is not available for all the units of
the group.
GROUP SETTING
01
•••
15
I.U. Add: Select by
depressing " "(TEMP)
switch.
(The main unit is set)
/
4
7

Publicidad

loading