Teach Procedure; External Teach (Teach-By-Wire); Teach From Io-Link Master; Single Point Mode Procedure - CARLO GAVAZZI CA30CAF BPA2IO Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 93

2.5. Teach procedure

2.5.1. External Teach (Teach-by-wire)

NB! This function works in single point mode and only for SP1 in SSC1.
The Teach-by-wire must be set-up first using an IO-link master:
a) Select: "2=Teach by wire" in the Selection of local/remote adjustment parameters 68 (0x44).
b) Select: "1=Single Point Mode" is already selected in "SSC1 Configuration" 61(0x3D),
"Mode 1" 2(0x02), (this value should already be set as default).
c) Select: 6=Teach-In (Active High) in Chanel 2 (SO2) 65 (0x41) sub index 1 (0x01).
Teach-by-wire procedure.
1) Place the target in front of the sensor and connect the teach-by-wire input (pin 2 white wire) to V+
(pin 1 Brown wire). The yellow LED LED will Flash with 1Hz (ON 100mS and OFF 900 mS).
2) Within 3-6 seconds the wire must be disconnected, and the yellow led is flashing with 1Hz (ON
900
mS and OFF 100 mS).
3) After successful teach the yellow LED will flash with 2 Hz (ON 250 mS and OFF 250 mS).
NB! If the Teach procedure is to be canceled do not remove the wire after 3 to 6 second but keep the
connection for 12 sec until the yellow LED is flashing with 10 Hz (On 50 mS and off 50 mS).

2.5.2. Teach from IO-Link Master

a) To enable teach from IO-Link master first disable the trimmer input:
Select: "0=Disabled" in the Selection of local/remote adjustment parameters 68 (0x44).
b) The individual team commands can be written to index 2.

2.5.2.1. Single point mode procedure

Select the Switching channel to be taught
a) Select: 1=SSC1 or 2=SSC2 in the "Teach-in Select" 58(0x3A) or 255 = All SSC.
b) Change the Hysteresis if requested for SSC1 or SSC2.
"SSC1 configuration" 61(0x3D) "Hysteresis" 3(0x03).
"SSC2 configuration" 62(0x3D) "Hysteresis" 3(0x03).
NB! It is not recommended to change the hysteresis below the values stated in the SSC
parameter list.
1) Single value teach command sequence:
#65 "SP1 Single value teach"
#64 "Teach apply" (optional command)
Command Sequence
1) "SP1 Single value Teach"
2) "Teach Apply"
SSC
Sensor
Rev.00 - 06.2018 | CA18/CA30 Capacitve sensors with IO-Link interface | © 2018 | CARLO GAVAZZI Industri
Sensing distance
17

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ca30caf bpm1io serieCa30can bpa2io serieCa30can bpm1io serieCa18caf bpa2io serieCa18caf bpm1io serieCa18can bpa2io serie ... Mostrar todo

Tabla de contenido