Wiring Diagrams; Commissioning - CARLO GAVAZZI CA30CAF BPA2IO Serie Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 93
2.7.11. Maintenance event counter
The sensor logs how many times the event counter have asked for maintenance, the maximum number
of events to be recorded are 2 147 483 647 times. This parameter is updated once per hour and can
be read from an IO-Link master.
2.7.12. Download counter
The sensor logs how many times the parameters have been changed in the sensor, the maximum
number of changes to be recorded are 65 536 times. This parameter is updated once per hour and
can be read from an IO-Link master.
NOTE!
The temperature measured by the sensor will always be higher than the ambient temperature, due to
internal heating.
The difference between ambient temperature and internal temperature is influenced by how the sensor
is installed in the application. If the sensor is installed in a metal bracket the difference will be lower
than if the sensor is mounted in a plastic one.

3. Wiring diagrams

PIN
Color
1
Brown
2
White
3
Blue
4
Black

4. Commissioning

50 ms after the power supply is switched on, the sensor is operational.
If it is connected to an IO-link master, no additional setting is needed and the IO-Link communication
starts automatically after the IO-Link master sends a wakeup request to the sensor.
24
Rev.00 - 06.2018 | CA18/CA30 Capacitve sensors with IO-Link interface | © 2018 | CARLO GAVAZZI Industri
1 BN
V
4 BK
2 WH
3 BU
V
Signal
Description
10 to 40 VDC
Sensor Supply
Load
Output 2 / SIO mode / External input / External Teach
GND
Ground
Load
IO-Link /Output 1 /SIO mode

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ca30caf bpm1io serieCa30can bpa2io serieCa30can bpm1io serieCa18caf bpa2io serieCa18caf bpm1io serieCa18can bpa2io serie ... Mostrar todo

Tabla de contenido