Descargar Imprimir esta página

Hitachi RASC Serie Manual De Instalación Y Funcionamiento página 31

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 45
REFRIGERANT PIPING &
REFRIGERANT CHARGE
Example in a Single and Twin systems:
Single system
+H
Maximum piping length according to the unit:
Mark
Unit
Actual piping length Equivalent piping length
RASC-3H(V)RNE
L
RASC-5/10HVRNE
L = Piping length.
NOTE:
-
Install the branch pipe at the location from where the piping
length to the indoor units is of equal distance. However,
when different piping lengths from the branch pipe to the
indoor units, due to building construction are required, the
difference between the two pipes should be less than 8 m.
-H
Maximum Piping Length
≤ 30 m
≤ 45 m
≤ 50 m
≤ 70 m
Twin system
+H
11.4.2. REFRIGERANT PIPING SELECTION
Select the piping connection sizes according to the following
procedures:
-
Between RASC unit and branch pipe:
Select the same pipe connection size as the pipe size of
the RASC Unit
-
Between branch pipe and Indoor Unit:
Select the same pipe connection size as the pipe size of
the Indoor Unit
Gas piping
Unit
size
piping size
RASC-3
15.88 (5/8")
9.53 (3/8")
RASC-5
15.88 (5/8")
9.53 (3/8")
RASC-10
25.4 (1")
12.7 (1/2")
For RASC-10HRNE units, use a reducer pipe in the following
installations:
Installation
Distributor
type
Single
-
Twin
TE-56N
Quad
QE-810N
PMML0140A rev.1 - 07/2009
NOTE:
-H
-
For Twin system:
L=C+(the longest
distance from
indoor unit to
branch pipe).
Distributor
Liquid
Twin
TE-03N
TE-56N
TE-10N
QE-810N
Pipe
Dimensions
Type
a
Gas
Ø 25.4
Liquid
Ø 12.7
Liquid
Ø 9.53
Liquid
Ø 12.7
Quad
-
-
b
Ø 22.2
Ø 9.53
Ø 6.35
Ø 9.53
31

Publicidad

loading

Este manual también es adecuado para:

Rasc-hrneRasc-hvrne