GROUNDING
THE
G EN ERATO R
The National Electrical Code requires that the frame and
external electrically conductive parts of this generator be
properly connected to an approved earth ground. Local
electrical codes may also require proper grounding of the
unit. For that purpose, a GROUNDING WING NUT is
provided on the generator end (Figure 3).
Wing Nut
I*
Turn the fuel valve to the "On" position (Figure 4).
Place the choke lever in the "Choke"
position
(Figure 5).
Generally, connecting a No. 12AWG (American Wire
Gauge) stranded copper wire to the grounding wing nut
and to an earth-driven copper or brass grounding rod
(electrode) provides adequate protection against electrical
shock. Be careful to keep the grounding wire attached after
connecting the stranded copper wire. However, local codes
may vary widely. Consult with a local electrician for
grounding requirements in your area.
Properly grounding the generator helps prevent electrical
shock if a ground fault condition exists in the generator or
in connected electrical devices. Proper grounding also helps
dissipate static electricity, which often builds up in
ungrounded devices.
OPERATING
THE
G EN ERATO R
_
AUTION!
Never start or stop the engine with
electrical loadsconnected to the receptacles AND
with the connected devices turned ON.
Starting
the Engine
Disconnect alt electrical loadsfrom the generator. Use the
following start instruction steps by numerical order:
3.
Set the rocker switch to "On" position (Figure 6).
4.
Grasp the recoil handle and pull slowly until slight
resistance is felt.Then pull rapidly to start engine.
5.
Move choke lever to "Run" position a short distanceat
a time over severalseconds in warm weather or
minutes in cold weather. Let engine run smoothly before
each change.Operate with choke in "Run" position.
NOTE: If engine still fails to start after 3 pulls, check for
proper oil level in crankcase.This unit is equipped with a
low oil device which prevents the engine from being
started. See engine manual.
Refer to the engine owner's manual for more
detailed starting instructions.
/