Connecting
Electrical
Loads
• Let engine stabilize and warm up for a few minutes after
starting.
• Plug in and turn on the desired 120 and/or 240 VottAC,
single phase,60 Hz electrical loads.
• Do Not connect 240Volt loads to the 120Volt duplex
receptacles.
• Do Not connect 3_hase loadsto the generator.
• Do Not connect 50 Hz loads to the generator.
• DO NOT OVERLOADTHE
GENERATOR.
See
"Don't Overload the Generator" on page 9.
Stopping the Engine
• Unplug all electrical loads from generator panel
receptacles.Never start or stop engine with electrical
devices plugged in and turned ON.
• Let engine run at no-load for several minutes to stabilize
the internal temperatures of engine and generator.
• Move rocker switch to "Off'
position.
• Move the fuel valve to the "Off'
position.
RECEPTACLES
120/240 Volt AC, 30 Amp,
Locking
Receptacle
Use a N EMA LI4-30 plug with this receptacle. Connect a
4-wire cord set rated for 250 Volt AC loads at 30 Amps (or
greater) (Figure 7).You can use the same 4-wire cord if you
_lanto run a 120Volt load.
NEMA LI4-30
' (Neutral)
Y (Hot)
|
X (Hot)
/
77_
Ground (Green)
This receptacle powers 120/240Volt AC, 60 Hz, single
phase loads requiring up to 5,500 watts of power (5.5 kW)
at 30 Amps for 120Volts or 240Volts.The outlet is
protected by a push-to-reset circuit breaker.
_
CAUTION!
Although this outlet states it has a
120/240Volt 30 Amp rating (up to 7,200 watts), the
generator is only rated for 5,500 watts. Powering
loads that exceed the wattage/amperage capacity of
the generator can damage it or cause serious
injuries.
120 Volt AC, 20 Amp,
Duplex
Receptacles
Each duplex receptacle (Figure 8) is protected against
overload by a push-to-reset circuit breaker.
I
I
Use each receptacle to operate 120Volt AC, single-phase,
60 Hz electrical loadsrequiring up to 2,400 watts (2.4 kW)
at 20Amps of current. Use cord sets that are rated for
125Volt AC loads at 20 Amps (or greater).
_
CAUTION!These
outlets are rated at 120Volt
20 Amp each (up to 80 Amps).The generator is only
rated for up to 45.8 Amps. Powering loads that
exceed the wattage/amperage capacity of the
generator can damage it or cause serious injuries.
/
8