Adjustment "empty"
During the empty adjustment, the probe have to has to be mounted in the correct position in the con-
tainer. The container is empty.
• By applying / connecting the teach wire to the supply voltage (UB+) or by holding the magnet to the
teach spot, the mode change is activated.
• The setting is made by disconnecting the teach wire or removing the magnet from the teach spot at the
menu item adjustment "empty", see Table 1 (setting menu).
• The teach input is inactive during initialization and setting.
• The setting is displayed via the LED and via the output.
Adjustment "empty" active
Adjustment "empty" successful
The empty measured value is saved.
Flashing frequency is increased by three levels depending on progress.
Adjustment "full"
During the empty adjustment, the probe have to be mounted in the correct position in the container. The
container is filled with any medium.
• By applying / connecting the teach wire to the supply voltage (UB+) or by holding the magnet to the
teach spot, the mode change is activated.
• The setting is made by disconnecting the teach wire or removing the magnet from the teach spot at the
menu item adjustment "full", see Table 1 (setting menu).
• The teach input is inactive during initialization and setting.
• The setting is displayed via the LED and via the output.
Adjustment "full" active
Adjustment "full" successful
The measured end value is saved, flashing frequency remains the same.
18
Time interval 3 to 8 seconds
LED green is flashing T=300 ms
Aout = 25 %
Aout = 50 %
Time interval 8 to 13 seconds
LED green flashing T=150 ms
Aout = 75 %
Aout = 100 %