Table Of Countries; Exclusion Of Liability - Steca Elektronik StecaGrid 2020 Instrucciones De Instalación Y Manejo

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

EN
13.3

Table of countries

Details on setting the country are provided in Section 8.7, P. 21.
Note
The requirements for the country-specific grid parameters may change at short notice. Contact the
Steca Customer Service if the parameters specified in Tab. 12 no longer correspond to the legally
prescribed requirements in your country. See Section Contact, P. 36.
Country
Name
Display
EN 50438 / 60 Hz
60438 EN50438 60Hz
LA 110 V / 60 Hz
11060 LA 110V 60Hz
LA 120 V / 60 Hz
12060 LA 120V 60Hz
LA 127 V / 60 Hz
12760 LA 127V 60Hz
LA 110 V / 50 Hz
11050 LA 110V 50Hz
LA 120 V / 50 Hz
12050 LA 120V 50Hz
LA 127 V / 50 Hz
12750 LA 127V 50Hz
Tahiti 110 V / 60 Hz
6891 Tahiti 60Hz
Droop Mode
0017 Droop Mode 60
110 V / 60 Hz
5)
Universal 120 V
0018 Universal
6)
Tab. 12: Table of countries
Country code and name as shown on the display.
1)
Disconnection values are upper and lower deviations from the peak values of the rated voltage
2)
(in %) and the associated switch-off time (in s).
Disconnection values are upper and lower deviations from the average values of the rated volt-
3)
age (in %) and the associated switch-off time (in s).
Disconnection values are upper and lower deviations from the rated frequency (in Hz) and the
4)
associated switch-off time (in s).
5)
Attention
Danger of yield losses. Activation of the Droop Mode is not permitted in systems connected to the
public electricity grid.
Activation of the Droop Mode is recommended when the inverter is operated in conjunction with
a stand-alone inverter in a system that is not connected to the public electricity grid.
Absolute frequency shut-off values:
6)
Upper value: 65 Hz
Lower value: 45 Hz
14

Exclusion of liability

The manufacturer can neither monitor compliance with this manual nor the conditions and methods
during the installation, operation, usage and maintenance of the inverter. Improper installation of
the system may result in damage to property and, as a result, to bodily injury.
Therefore, we assume no responsibility or liability for loss, damage or costs which result from, or are
in any way related to, incorrect installation, improper operation, or incorrect use and maintenance.
Similarly, we assume no responsibility for patent right or other right infringements of third parties
caused by usage of this inverter.
The manufacturer reserves the right to make changes to the product, technical data or installation
and operating instructions without prior notice.
As soon as it becomes evident that safe operation is no longer possible (e.g. visible damage), re-
move the device from the grid and the photovoltaic generator immediately.
34
Voltage disconnection
values (peak values)
upper
s
%
s
1)
20
15
0,2
20
15
0,2
20
15
0,2
20
15
0,2
20
15
0,2
20
15
0,2
20
15
0,2
30
15
0,2
60
20
0,5
20
25
2,0
Voltage disconnec-
tion values ø (aver-
2)
age values)
lower
upper
%
s
%
s
–15
1,5
–15
0,2
–20
0,2
–20
0,2
–15
0,2
–20
0,2
–20
0,2
–15
0,2
–20
0,5
–25
2,0
Frequency discon-
nection values
3)
lower
upper
lower
%
s
Hz
s
Hz
1,0
0,5
–3,0
1,5
0,2 –3,0
1,5
0,2
–3,0
1,5
0,2
–3,0
1,5
0,2
–3,0
1,5
0,2
–3,0
1,5
0,2 –3,0
2,5
0,2 –5,0
5,0
0,5
–3,5
0,5
6)
744.711 | 12.20
4)
s
0,5
0,2
0,2
0,2
0,2
0,2
0,2
0,2
0,5
0,5
6)