Descargar Imprimir esta página

Carel thTx Manual Del Usuario página 20

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

ENG
Serial interface
RS485 serial interface for communication with the controllers. Use AWG
20 to 22 shielded wire. The total length of the network must not exceed
500 m. The power supply wires must be between 0.5 mm
Up to 32 terminals can be connected. For large networks, place a 120
Ohm resistor between A (RX/TX+) and B (RX/TX-) on the last device, to
avoid possible communication problems.
Exploded view
thTx 24 Vac/dc network confi guration
L
N
thTx
B (-)
A (+)
GND
V+
230 Vac
V-
thTx 230 Vac network confi guration
L
N
thTx
n.1
B (-)
A (+)
GND
"manuale thTx" +0300141IE rel. 1.0 - 16.01.2024
2
and 1.5 mm
Fig. 1.g
M
Fan
thTx
Valve
n.1
n.2
EH
EM EL VC V0
COM
B (-) A (+)
G
V-
V+
24 Vac
M
Fan
thTx
Valve
n.2
EH
EM EL VC V0
COM
B (-) A (+)
G
N L
Disassembly
Insert a screwdriver into the groove on the bottom and press outwards
to detach the display.
2
.
General notes
Avoid installing the device in environments with the following
characteristics:
• relative humidity higher than the specifi ed value;
• strong vibrations or knocks;
• exposure to water sprays;
• exposure to aggressive and polluting atmospheres (e.g.: sulphur and
ammonia gases, saline mist, smoke) which may cause corrosion and/
or oxidation;
• strong magnetic and/or radio frequency interference (thus avoid instal-
lation near transmitting antennae);
• exposure to direct sunlight and the elements in general;
• wide and rapid fl uctuations in room temperature;
• environments where explosives or fl ammable gas mixtures are present;
• exposure to dust (formation of corrosive patina with possible oxidation
and reduction of insulation).
M
Fan
Valve
EH
EM EL VC V0
COM
B (-) A (+)
G
V- V+
Fig. 1.h
M
Fan
Valve
EH
EM EL VC V0
COM
B (-) A (+)
G
N L
Fig. 1.i
8
M
Fan
thTx
Valve
n.32
EH
EM EL VC V0
COM
B (-) A (+)
G
V- V+
120 Ω
M
Fan
thTx
Valve
n.32
EH
EM EL VC V0
COM
B (-) A (+)
G
N L
120 Ω

Publicidad

loading