The device must be installed, operated and stored in a room with a surface area greater than 4m2. The
device must not be installed in a space without ventilation, if that space is less than 4m2.
• Reusable mechanical connectors and flared joints are not allowed indoors. (Requirements of the
EN standard).
• Mechanical connectors used indoors must have a rate of no more than 3g / year at 25% of the maximum
allowable pressure. When mechanical connectors are reused indoors, the sealing parts must be renewed.
When fiare joints are reused indoors, the fiare part must be remanufactured. (Requirements of UL standard)
• When mechanical connectors are reused indoors, the sealing parts must be renewed. When fiare seals are
reused indoors, the fiare part must be remanufactured. (IEC Standards Requirements)
WARNING FOR THE USE OF R-32 REFRIGERANT
• When flammable refrigerant is used, the appliance must be stored in
a well ventilated area where the size of the room corresponds to the area
of the room as specified far its operation. For R-32 refrigerant models:
1 PRECAUTIONS AND WARNINGS