Descargar Imprimir esta página

ABB ACH580-34 Guía Rápida De Instalación Y Puesta En Marcha página 12

Ocultar thumbs Ver también para ACH580-34:

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 41
12 EN – Quick installation and start-up guide
Install the drive module and LCL filter module into an
enclosure
See
Installing the drive module and LCL filter module into a Rittal VX25
enclosure (page 129)
Step
Tasks
Mechanical accessories
1
Attach the plinth to the floor.
2
Attach the enclosure frame to the plinth.
3
Make the bottom plate with 360-degree grounding entries for power cables. Attach the bottom
plate to the enclosure frame.
EN
4
Attach the punched section to the back of enclosure frame.
DE
5
Attach the mounting brackets to the punched section.
LCL filter module
ES
6
Install the pedestal to the LCL filter module.
FR
7
Install the cooling fan to the LCL filter module.
8
Attach the LCL filter module pedestal guide plate to the enclosure bottom plate.
IT
9
Attach the drive module pedestal guide plate to the enclosure bottom plate.
TR
10
Attach the extraction/installation ramp to the LCL filter module pedestal guide plate.
11
To prevent the LCL filter module from falling, attach its lifting lugs with chains to the enclosure
frame.
12
Push the LCL filter module carefully into the enclosure along the extraction/installation ramp.
Work preferably with help from another person as shown below. Keep a constant pressure
with one foot on the base of the module to prevent the module from falling on its back.
13
Unfasten the extraction/installation ramp and attach the LCL filter module to bottom plate.
Drive module
14
Attach the extraction/installation ramp to the drive module pedestal guide plate.
15
Remove the sheeting from the clear plastic shrouds (option +B051) of the drive module from
both sides.
16
Install the top metallic shroud to the drive module.
17
Install the back shrouds to the drive module.
.

Publicidad

loading