Descargar Imprimir esta página

Mitsubishi Electric MXZ-4F83VF2 Manual De Instalación página 9

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 51
2. OUTDOOR UNIT INSTALLATION
2-1. INSTALLING THE UNIT
• Be sure to fix the unit's legs with bolts when installing it.
• Be sure to install the unit firmly to ensure that it does not fall by an earthquake or a gust.
• Refer to the figure in the right for concrete foundation.
• Do not use the drain socket and the drain caps in the cold region.
Drain may freeze and it makes the fan stop.
• Remove the tape on the panel when opening the package. (DO NOT remove the LABELS on the panel.)
Make the setting
depth deeper.
2-2. CONNECTING WIRES FOR OUTDOOR UNIT
1) Remove the service panel and the cable cover.
2) Pass the indoor/outdoor unit connecting wire (B) and power supply cord (A)
through the grommet. Loosen terminal screw, and connect indoor/outdoor unit
connecting wire (B) from the indoor unit correctly on the terminal block. Be
careful not to make mis-wiring. Fix the wire to the terminal block securely so
that no part of its core is appeared, and no external force is conveyed to the
connecting section of the terminal block.
3) Firmly tighten the terminal screws to prevent them from loosening. After
tightening, pull the wires lightly to confirm that they do not move.
4) Perform 2) and 3) for each indoor unit.
5) Connect power supply cord (A).
6) Fix indoor/outdoor unit connecting wire (B) and power supply cord (A) with
the cable clamps. Route the cables or wires so as not to deform the service
panel. Otherwise, rainwater may enter the outdoor unit.
7) Close the service panel and the cable cover securely. Make sure that 3-3.
PIPE CONNECTION is completed.
• After making connections between both power supply cord (A) and indoor/
outdoor unit connecting wire (B), be sure to fix both cable and wire with cable
clamps.
Connecting order
• Connect the terminal block in following order.
Power supply
Terminal block for
indoor/outdoor unit
Indoor/outdoor unit
connecting wire
<OUTDOOR UNIT>
Terminal block
Terminal block
<INDOOR UNIT>
• Be sure to attach each screw to its correspondent terminal when securing the cord and/or the wire to the terminal block.
• Make earth wire a little longer than others. (More than 35 mm)
• For future servicing, give extra length to the connecting wires.
Fix here with
M10 bolts.
Make width wider.
MXZ-5F102VF2
MXZ-4F83VF2
Terminal block for
power supply
Terminal block
POWER SUPPLY
~/N 220-230-240 V 50 Hz
Terminal block
Anchor leg
Anchor bolt length
Anchor bolt pitch
Service panel
A → B → C → D → E → P
A → B → C → D → P
15 mm
35 mm
Lead wire
600
(Unit: mm)
Terminal block
for power supply
5F102VF2
Screws
INDOOR /
Model
OUTDOOR UNIT
A – E
MXZ-5F102VF2
A – D
MXZ-4F83VF2
en
Cable
cover
Cable clamp
7

Publicidad

loading

Este manual también es adecuado para:

Mxz-5f102vf2