Troubleshooting - Parker Hiross Hyperchill ICE001 Manual De Uso

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

English
6

Troubleshooting

THE OUTLET WATER
TEMPERATURE
EXCEEDS THE SET
VALUE
EXCESSIVE
WATER
FLOW, HIGH
THERMAL LOAD
YES
REDUCE THE
FLOW RATE OF
THE WATER TO
BE COOLED
AMBIENT
TEMPERATURE
RETURN THE
AMBIENT
TEMPERATURE TO
BELOW THE
SPECIFIED LIMIT
FAULT
COMPRESSOR STOPS DUE
TO OPERATION OF THE
HIGH PRESSURE SWITCH
PRESSURE
SWITCH
BROKEN OR
WRONGLY
CALIBRATED
NO
YES
NO
REPLACE
PRESSURE SWITCH
HIGH
CONDENSER
NO
NO
FINS
DIRTY
YES
YES
CLEAN THE FINS
OF THE
CONDENSER
CAUSE
REMEDY
COMPRESSOR SUCTION,
LIQUID LINE
FROSTED UP
NO
REFRIGERANT
INSUFFICIENT
FILTER
WATER FLOW
CLOGGED
YES
YES
INCREASE THE
FLOW RATE OF
REPLACE
THE FLUID TO
THE FILTER
BE COOLED
CONDENSER
SURFACES
CLOGGED
YES
CLEAR THE FRONT
SURFACE
OF THE
CONDENSER
Hyperchill (ICE001)
COMPRESSOR
RUNS FOR
LONG PERIODS,
NOISY
COMPRESSOR
COMPONENTS
DETERIORATED
YES
REPAIR OR
REPLACE
COMPRESSOR
LEAKS IN
REFRIGERANT
NO
CIRCUIT,
FILTER
SYSTEM
CLOGGED
DISCHARGED
YES
CHECK
FOR LEAKS,
REPLACE
ELIMINATE THEM,
THE FILTER
CHARGE
THE CIRCUIT
14
NO
YES