10. Detailed settings
3. Select the settings that are to be reset and confirm with [↵].
Instrument data
Instrument settings will be reset to their as-delivered condi-
tion.
Drag pointer
The drag pointer values are reset.
4. Confirm reset with [↵].
» The settings are reset.
10.7 Setting the HART
10.7.1 Setting the short address (multidrop mode)
Setting range: 0 ... 63
1. Open the operating menu with [↵].
Select "Detail setup" and confirm with [↵].
2. Select "HART" and confirm with [↵].
3. Select "Short addr." and confirm with [↵].
4. Change digit using [▲] [▼] and confirm with [↵]. The cursor
moves to the next digit. Repeat for each digit.
» Short address is set.
10.7.2 Activating/deactivating constant current
The constant current affects the output of current values, e.g. in the additional
display.
WIKA operating instructions, model DMSU22SA
communication
EN
41