10. Detailed settings
1. Open the operating menu with [↵].
Select "Detail setup" and confirm with [↵].
2. Select "HART" and confirm with [↵].
3. Select "Cons. current" and confirm with [↵].
EN
4. Activate/deactivate constant current.
Select "on" or "off" and confirm with [↵].
» Constant current is activated/deactivated.

10.8 Alarm status of diaphragm monitoring

In the event of a leakage at the sensor tube, the pressure monitored in the interstitial
space increases. As soon as the specified set point is exceeded, the alarm signal for a
sensor break is transmitted.
If a sensor break is detected, the instrument must be replaced immediately.
→ See chapter 14 "Dismounting, return and disposal".

10.8.1 Alarm message at the display and operating unit

The additional display changes to the alarm
message with the plain-text message "Diaphragm
rupture". As shown on the right, an additional
warning symbol is displayed in the upper area of
the LC display.
The main display remains unchanged.
42
WIKA operating instructions, model DMSU22SA