11 | Mantenimiento y resolución de fallos
Fault
Possible cause
In spite of high radiation
Particular ambient con-
levels, the inverter does
ditions.
not feed the maximum
power into the grid.
DC fuse defective
Tab. 6: Troubleshooting
B = Operator's responsibility ; E = The indicated work may only be carried out by an authorised electrician. ; K = The in-
dicated work may only be carried out by a service employee of KACO new energy GmbH!
11.8
Fault messages
Many fault signals indicate a fault in the grid. They are not operational faults of the device. The triggering levels
are defined in standards, e.g. VDE0126-1-1. The device shuts down if the values exceed or fall below the appro-
ved levels.
Fault LED (red)
Status
FS (fault status)
OS (operating status)
11.9
Troubleshooting
The following table lists the possible status and fault messages, the ProLog© status messages that the device
can display by means of the LC display / web interface and the LEDs.
N.° LED
LED
Visualización de pantalla
red
AVISO
Fault number not found?
If fault numbers are displayed on the device but are not listed here, then it is usually necessary to have this loo-
ked at by your installation partner.
Página 82
Explanation/remedy
Because the temperatures inside the device are too high, the
device reduces its power to prevent damage to the device. No-
te the technical data. Ensure that the convection cooling is not
impeded from the exterior. Do not cover the cooling fins.
› Ensure sufficient cooling of the device.
Remove any foreign bodies which are present on the unit.
› Clean the cooling fins
A generator string is disconnected from the device owing to a
faulty fuse. Check why it has tripped by measuring all DC
strings using a clip-on ammeter. If there is no current flow in a
string, the associated DC fuse is faulty.
Check the no-load voltage and dimensioning of the PV genera-
tor. Replace any damaged modules.
› Replace the PV fuse with a fuse of the same size and type.
Explanation
– Fault signal relay has been tripped.
– Feed-in was ended due to a fault.
– The fault relay releases again.
– The device feeds back into the grid again after a country-
specific time period.