VII.
SPECIFICATIONS
Paramete
Load Rating
Voltage Protection
Rating (VPR)
Attenuation Normal
Mode
Common
Mode
Power Requirement
(no load)
Under-Voltage
Shutdown
Over-Voltage
Shutdown
Internal Memory Capacity
Timestamp Accuracy
Voltmeter Accuracy
(Peak Reading Type)
Response Time
Under-Voltage
Record Definition
Over-Voltage Record
Definition
Power Outage Event Definition
© 2022 AMETEK Electronic Systems Protection / Technical Support: 1-800-645-9721 / espsurgex.com
XG-PCS-15D
15 Amps at 120 Volts
XG-PCS-20D
20 Amps at 120 Volts
XG-PCS-20815D
15 Amps at 208-240 Volts
XG-PCS-20820D
20 Amps at 208-240 Volts
XG-PCS-23013
13 Amps at 230V
XG-PCS-L630
30 Amps at 208-240 Volts
XG-PCS-630
30 Amps at 208-240 Volts
XG-PCS-15D
330V All Modes
XG-PCS-20D
XG-PCS-20815D
800V Line-Line
XG-PCS-20820D
500V Line-Ground
XG-PCS-23013
N/A
XG-PCS-L630
800V Line-Line
XG-PCS-630
500V Line-Ground
XG-PCS-15D
> 30 dB 80kHz – 50MHz
XG-PCS-20D
XG-PCS-20815D
XG-PCS-20820D
XG-PCS-23013
XG-PCS-L630
XG PCS 630
XG-PCS-15D
> 30 dB 70kHz – 50MHz
XG-PCS-20D
XG-PCS-20815D
> 30 dB 200 kHz – 50MHz
XG-PCS-20820D
XG-PCS-23013
XG-PCS-L630
XG PCS 630
XG-PCS-15D
4 Watts
XG-PCS-20D
XG-PCS-20815D
XG-PCS-20820D
XG PCS 23013
XG-PCS-L630
6 Watts
XG-PCS-630
120V Models
Adjustable from 80V to 95 V, or Disabled. Restores at 105V.
208-240V Models
Adjustable from 140V to 170 V, or Disabled. Restores at 190V.
120V Models
Adjustable from 135V to 160V. Restores at 130V.
208-240V Models
Adjustable from 260V to 300V. Restores at 250V.
60 Events with timestamp; 999 counts of each event type
± 2.5%
120V Models
± 5% Typical product accuracy between 40V and 180V
208-240V Models
± 5% Typical product accuracy between 100V and 300V
Over-Voltage
100 msec
Under-Voltage
150 msec
120V Models
AC Voltage has dropped below 100V
208-240V Models
AC Voltage has dropped below 180V
120V Models
AC Voltage has risen above 135V
208-240V Models
AC Voltage has risen above 260V
AC Voltage has dropped below 20V
User Manual
Specificatio