Condensate Drain Connection; Service And Maintenance - Ferroli ECONCEPT TECH 18 A Instrucciones De Uso

Ocultar thumbs Ver también para ECONCEPT TECH 18 A:
Tabla de contenido

Publicidad

Idiomas disponibles
  • MX

Idiomas disponibles

  • MEXICANO, página 11
Table. 7 - Typology
Type
Description
C2X
Intake and exhaust in common flue (intake and exhaust in same flue)
C4X
Intake and exhaust in common and separate flues , but undergoing similar wind conditions
C8X
Exhaust in single or common flue and wall intake
B3X
Intake from installation room by means of concentric duct (that encloses the exhaust) and exhaust in
common flue with natural draught
IMPORTANT - THE ROOM MUST BE PROVIDED WITH APPROPRIATE VENTILATION
If the boiler is to be connected ECONCEPT TECH 18 A to a collective flue or a single
flue with natural draught, the flue or chimney must be expressly designed by profession-
ally qualified technical personnel in conformity with the current regulations and be suita-
ble for sealed chamber units equipped with fan.

3.7 Condensate drain connection

The boiler has an internal trap for draining condensate. Fit the inspection union A and
the hose B, pressing it in. Fill the air-trap with approximately 0.5 l. of water and connect
the hose to the disposal system
B
ATTENTION: The unit must never be operated with the trap empty!
A
B
fig. 16 - Condensate drain connection

4. SERVICE AND MAINTENANCE

4.1 Adjustments
Gas conversion
The unit can operate on Natural Gas or LPG and is factory-set for use with one of these
two gases, as clearly shown on the packing and on the dataplate. Whenever a different
gas to that for which the unit is arranged has to be used, a conversion kit will be required,
proceeding as follows:
1.
Remove the casing.
2.
Open the sealed chamber.
3.
Release the fixing clip C and remove gas pipe A from the fan - venturi assembly.
4.
Replace nozzle B, inserted in the gas pipe, with that contained in the conversion kit.
5.
Reassemble gas pipe A with the clip and check the seal of the connection.
6.
Apply the label, contained in the conversion kit, near the dataplate.
7.
Refit the sealed chamber and casing.
8.
Modify the parameter for the type of gas:
put the boiler in standby mode
press the DHW buttons (detail 1 - fig. 1) for 10 seconds: the display shows
"P01" flashing.
press the DHW buttons (detail 1 - fig. 1) to set parameter 00 (for use with nat-
ural gas) or 01 (for use with LPG).
press the DHW buttons (detail 1 - fig. 1) for 10 seconds.
the boiler will return to standby mode
9.
Using a combustion analyser connected to the boiler fume outlet, check that the
CO2 content in the fumes, with the boiler operating at max. and min. output, match-
es that given in the technical data table for the corresponding type of gas.
32
EN
0,5lt
cod. 3540R794 - Rev. 02 - 02/2015
ECONCEPT TECH 18 A
fig. 17 - Gas conversion
TEST mode activation
Press the heating buttons (detail 3 - fig. 1) at the same time for 5 seconds to activate the
TEST mode. The boiler lights at the maximum heating power set as described in the fol-
lowing section.
The heating and DHW symbols (fig. 18) flash on the display; the heating power will be
displayed alongside.
fig. 18 - TEST mode (heating power = 100%)
Press the heating buttons (detail 3 - fig. 1) to increase or decrease the power (Min.=0%,
Max.=100%).
Press the DHW button "-" (detail 1 - fig. 1) and boiler power is immediately adjusted to
min. (0%). Press the DHW button "+" (detail 1 - fig. 1) and boiler power is immediately
adjusted to max. (100%).
If the TEST mode is activated and enough hot water is drawn to activate the DHW mode,
the boiler remains in TEST mode but the 3-way valve goes to DHW.
To deactivate the TEST mode, repeat the activation sequence.
The TEST mode is automatically disabled in any case after 15 minutes or on stopping of
hot water drawing (if enough hot water was drawn to activate DHW mode).
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the
heating buttons (detail 3 - fig. 1) to increase or decrease the power (min. = 00 - max. =
100). Press the reset button within 5 seconds and the max. power will remain that just
set. Exit TEST mode (see sec. 4.1).

Publicidad

Tabla de contenido

Solución de problemas

loading

Tabla de contenido