2.2.3
MACHINE WALL INSTALLATION BRACKET
The bracket is supplied as assembly kit including the bolts for securing it to the machine.
This is a safety device that must be installed with the unit and secured to a structural
section of the installation site (wall, frame, etc.), to avoid the risk of overturning of the unit
due to external causes (accidental collision, earthquake, etc.).
Wall fastening screws not supplied.
Sizes in millimetres
2.2.4
CONDENSATE TANK (UNDER VERSION)
Additional Under version peraluman collection tank.
This component must be treated as a safety device, installed in the floor under the machine,
to collect any water leaks.
The water sensor must be installed by the installer in the collection tank
The tank has a Ø 22mm drain.
Sizes in millimetres
2.2.5
FREE SPACE AROUND THE INSTALLATION
OBLIGATION
Correct installation of the machine requires compliance with the
clearances shown in the figure. This allows ease of access to the
components of the machine for the purpose of normal inspection
and maintenance operations.
Units may be installed side by side.
Internal access is at the front for all sizes (F1, F2, F3).
UNDER
850
Sizes in millimetres
UM_s-MEXT_G00_01_Z_07_21_ML
Collection tank with water
sensor
850
21
OVER
850
Sizes in millimetres
2.2.6
MINIMUM INSTALLATION AREA FOR UNITS WITH R32
In case of installation in confined rooms, it's necessary to grant a minimum installation area
in order to prevent any above-limits concentrations in case of R32 leakage.
The unit must be installed in a room with a minimum surface, based on the following matrix
006 F1
009 F1
≤8 m²
-
-
≥8 m²
-
Room
surface A
≥15 m²
≥21 m²
installation allowed
The system installation is in accordance to EN378-1:2016 and, referring to Chapter 5.:
The Location Classification is: II
Access Category: c and less the 1 persone per 10m
For any room that doesn't fulfill the minimum area requirements, please contact our
technicians in order to find an alternative solution, in line with the EU regulations.
2.2.7
AIR CIRCULATION OBSTACLES FOR UNDER / OVER MACHINES
OVER
UNDER
Sizes in millimetres
TRANSLATION OF THE ORIGINAL INSTRUCTIONS
English
850
s-MEXT-G00 model
013 F1
022 F2
028 F3
038 F3
-
-
-
-
-
-
-
-
-
-
-
-
forbidden to install
2
044 F3
-
-
-