Alert Code Alert Text
4.1
WLS ERR
4.2
WATER LOW
4.3
NO WATER
4.4
OVER FILL
5.7
EXIT T ERR
Description
Possible Causes & Remedies
The water level sen-
1. Disconnect power and check the water level sen-
sor appears to be
malfunctioning.
2. Replace water level sensor if necessary.
The water level is get-
Refill the water reservoir soon.
ting very low.
The water level is too
Refill the water reservoir to continue normal operation.
low to continue cooling.
The water level ap-
1. Shut off the water supply.
pears to be too high.
2. Check that the float shutoff valve is positioned
3. Turn on the water supply and check for leaks when
The Exit Temperature
The exit air temperature sensor is located in the wiring
Sensor is not func-
harness of the water level sensor.
tioning correctly.
1. Disconnect power and check the water level sensor
2. Replace water level sensor if necessary.
ALERT CODES
sor connector. Clean and reconnect.
straight up and down, adjust if necessary.
the float is in the top (off) position. Replace if
necessary.
connector. Clean and reconnect.