OPERATION MODE SELECTION (SW2)
DIP1: automatic or step-by-step closing mode
• DIP1=ON: automatic mode (the barrier closes
automatically after the standby time has passed,
which is adjusted using T.E.).
• DIP1=OFF: step-by-step mode (the barrier only
closes when receiving the key command).
DIP2 (AEP1-008 / AEP1-08M): step-by-step or
collective opening
• DIP2=ON: step-by-step opening (the barrier can
be stopped by operating the command device
during opening. The barrier closes if pressed again).
• DIP2=OFF: collective opening (the panel does not
obey the command device during opening).
11
STARTING UP
Closing thrust check
Installation must respect the values indicated
in Standard EN 12453:2000. All measurements
must be made in line with the method
described in Standard EN 12445:2000.
• F
< 400N in all cases
d
DIP2 (AEP1-009 / AEP1-09M): reverse impulse
• DIP2=ON: reverse impulse enabled (when
opening begins, there is a small backward
movement of the leaf in order to help release
the electrolock).
• DIP2=OFF: reverse impulse disabled.
DIP3: automatic mode optional (only if DIP1=ON)
• DIP3=ON: during standby, the barrier obeys the
command device (this can be closed before standby
time finishes).
• DIP3=OFF: the barrier cannot be closed until
standby time finishes.
User instruction
1 Instruct the user with regards to the use and
maintenance of the installation and provide him/her
with the user guide.
2 Signpost the barrier, showing that it opens
automatically and indicating how to operate it
manually.
Where
appropriate,
operation is using the remote control.