5.2 Connection of the power supply
The pump must be protected on-site (min. 10 A, slow)
and must be connected to an external mains switch.
All cables used must have a heat resistance of up to 85 °C.
They must not be in contact with the pipe or the pump
and motor casing.
All cables must be connected in accordance with EN 60204-1
and EN 50174-2: 2000.
The electrical connection must be made as indicated
on the nameplate. For simpler subsequent replacement,
we recommend strapping the cable.
ModulA...RED, ModulA BLUE
ModulA 40-10 220
ModulA 40-12 250, ModulA-D 40-12 250 0.18 – 1.91
ModulA 40-18 250, ModulA-D 40-18 250 0.18 – 2.63
ModulA 50-6 240,
ModulA-D 50-6 240
ModulA 50-12 270, ModulA-D 50-12 270 0.21 – 2.32
ModulA 50-18 270, ModulA-D 50-18 270 0.21 – 3.34
ModulA 65-8 270,
ModulA-D 65-8 340
ModulA 65-12 340, ModulA-D 65-12 340 0.22 – 3.32
ModulA 65-15 340, ModulA-D 65-15 340 0.28 – 5.68
ModulA 80-8 360,
ModulA-D 80-8 360
ModulA 80-12 360, ModulA-D 80-12 360 0.32 – 5.56
ModulA 100-12 450, ModulA-D 100-12 450 0.32 – 6.78
L
FI
N
Example of a typical mains connection, 1×230 V ±10%, 50/60 Hz
Nominal
current
[A]
0.19 – 1.54
0.21 – 1.09
0.24 – 2.10
0.29 – 3.08
External switch
Protection
(min. 10 A, slow)
Output P
1
[W]
18 – 341
17 – 421
16 – 594
21 – 236
20 – 516
22 – 742
22 – 464
21 – 736
30 – 1254
29 – 704
32 – 1282
35 – 1563