5.5 Configuration with DIP switches (see appendix D)
Some settings can be changed with DIP switches.
Procedure:
a) Turn the Compact on, preferably without load and without AC voltage on the inputs. The
Compact will then operate in inverter mode.
b) Set the DIP switches as required.
c) Store the settings by moving DIP switch 8 to 'on' and back to 'off'.
5.5.1. DIP switch 1 and 2
Default setting: to operate the product with the 'On/Off/Charger Only' switch
ds 1: 'off'
ds 2: 'on'
The default setting is required when using the 'On/Off/Charger Only' switch in the front
panel. This setting should also be used in setups with a GX device or VE.Bus Smart
dongle when no additional Digital Multi Control panel or VE.Bus BMS is connected.
When a Digital Multi Control panel or a VE.Bus BMS is included please refer to the
settings below.
Setting for remote operation with a Multi Control Panel or a VE.Bus BMS:
ds 1: 'on'
ds 2: 'off'
This setting is required when a Multi Control Panel and/or a VE.Bus BMS is connected.
The Multi Control panel must be connected to one of the two RJ45 sockets B, see
appendix A.
Setting for remote operation with a 3-way switch:
ds 1: 'off'
ds 2: 'off'
This setting is required when a 3-way switch is connected.
The 3-way switch must be wired to terminal H, see appendix C.
Only one remote control can be connected, i.e. either a switch or a remote control panel.
In both cases the switch on the product itself should be 'on'.
18