1.6.2
Preparing the AC connection
You have completed the assembly.
1 Choose the proper seal accessory. The part seal recommended outer diameter of the cable (fig. 9 / pos. 1) is 20 – 24 mm.
The part seal recommended outer diameter of the cable (fig. 9 / pos. 2) is 24.5–30 mm.
2 The recommended cable type is YJVR or YJV. Strip the cable [95 – 100mm] and lead the cable through the cover.
» Make the electrical connections.
3 Strip the wires N, L1, L2, L3, PE by 20 – 25 mm.
Fig. 9: Choose the proper seal
Make AC connection
AC cable has been prepared.
1 Guide the configured cable through the nut and cover (fig. 11 pos. 1 & 2) and attach to the contact carrier (fig. 11/pos. 3)
with the enclosed Allen key [ A_3 /
2 Push the cover (Fig. 11. Pos 3) over the plug with the hole of the cover being visible (Fig. 12).
3 Tighten the nut with an open-ended wrench and complete the installation with a "click, click" [ W_50 /
NOTE: The AC connection is secure when an audible click is heard. (fig. 13)
4 When the nut is fully screws in, the locking ring can be twisted to lock the nut in place.
5 Lay the cables correctly and in accordance with the following rules:
– Lay the cables around the device with a minimum clearance of 30 cm.
– Never lay cables over semiconductors (heat sinks)
– Excessive bending force may negatively impact the protection rating. Lay the cables with a bending radius of at least
»
four times the cable diameter.
The device is connected to the power grid.
Fig. 11: Connecting wires
Legend
1
Seal
2 Contact carrier
Page 8
KACO blueplanet 25.0 NX3 M2 KACO blueplanet 30.0 NX3 M2 KACO blueplanet 33.0 NX3 M2
Fig. 10: Prepare the cable
4.0 Nm].
Fig. 12: Press the cover
3 Cover
4 Nut
10.0 Nm]
Fig. 13: Tighten the nut