Personalization Using External Software - MGE Pulsar M 2200 RT 2U Manual De Instalación Y De Usuario

Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Pulsar M
Output Personalization
Function
(1)
Output voltage
Frequency converter
(1)
Output frequency
Transfer to the bypass
(1)
AC input
(1)
Overload level
ON/OFF Personalization
Function
Start on battery power
Automatic restart
Energy savings
Detection of phase/
neutral inversion (SWF)
Battery Personalization
Function
Battery test
Selection of the backup
time
Battery protection
against excessive
discharges
4.4

Personalization Using External Software

Insert the Solution-Pac CD-ROM in the drive.
On the first navigation screen, select "Point to Point solution" and follow the instructions on how to install the Personal
Solution-Pac software.
Then select "Settings", "Advanced settings" and "UPS settings".
Note that the Linux/Unix/MacOS versions of the Personal Solution-Pac software do not offer this possibility.
(1). These Parameters may be modified only when the UPS is OFF.
(2). Bypass is disabled when frequency converter is enabled.
4 — 2
Factory Setting
120 Volts AC
(1)
Disabled
Automatic selection
Bypass AC power must be
within tolances
102%
Factory Setting
Enabled
Enabled
Disabled
Enabled
Factory Setting
Weekly test
Automatic detection of
number of battery modules
Enabled
Access to Maintenance and
Personalization Data
Comments
Options
100/104/110/120/125
The connected devices are never
transferred to the bypass.
Volts AC
User selectable only if the frequen-
(2)
Enabled
cy-converter function is enabled.
50 or 60 Hz
Bypass AC power may be
outside tolerances
50 / 70%
Alarm if threshold is overrun.
Options
Comments
Disabled
The UPS restarts automatically
Disabled
when AC power returns.
When function enabled, battery
Enabled
shuts down when power drops
to <5%.
When function enabled, the UPS
Disabled
remains OFF if the system detects
phase/neutral inversion.
Options
Comments
No test / daily test /
monthly test
UPS restarts automatically when
0 to 200 Ah
Normal AC source is restored.
When function disabled, MGE Office
Disabled
Protection Systems warranty no
longer applies.