Technical specifications
Mechanical specifications
Class of protection
Environment
Installation height
Mounting
Storage temperature
Operating environment
temperature
Air humidity
Electrical specifications
Rated voltage
Rated insulation voltage
Short-term current
Rated conditional short
circuit current
Power
Standards
IEC/EN 61439-1
12
COV BOX M, QC/AV, QC/AVE
IP 50
Environment B pursuant
to IEC/EN 61439-1
max. 2000 m above sea
level
Wall mounting
from -25°C to +55°C
from -5°C to +55°C
50% at 55°C (without
condensation)
1~ / 50Hz
220 - 240V ±10%
400V AC
1,5 kA
1 kA
0,37 - 4,0 kW
Doc. Name: ManualeQuadriControllo2018 / Rev. Date: 3/10/2018
COV BOX T
IP 50
Environment B pursuant
to IEC/EN 61439-1
max. 2000 m above sea
level
Wall mounting
from -25°C to +55°C
from -5°C to +40°C
50% at 55°C (without
condensation)
3~ / 50Hz
380V -10% / 415V +6%
400V AC
50 kA
50 kA
0,37 - 7,5 kW

Publicidad