a) Power connections:
POWER SUPPLY
220-240V Single Phase (L + N)
220-240V Three Phase (L1 + L2 + L3)
380-420V Three Phase (L1 + L2 + L3)
b) Conexiones de señales
Signal
Description
Outputs that act (the contact closes) as programmed in the settings
Relays 1 and 2
menu of 9. OUTPUT RELAYS.
(OUT 1, OUT 2)
These outputs are potential free and support a maximum load of 5A at
230Vac.
This input is used in case you need to enable the equipment through
an irrigation controller.
Irrigation
Requires an external signal up to 48V (AC or DC) and must be ena-
controller
bled in the menu 6. FINE SETTINGS, as long as the application type is
(IN 24Vac)
BOOSTER SET, BOREHOLE PUMP or COMBINED.
In the COMBINED application type, the irrigation controller only will
have an effect on the operation of pump 2.
Pressure transducer or level control device (4-20mA) connection and
maintaining polarity shown in the transducer connection drawing.
Pressure
This input must be enabled in menu 5. TYPE OF APPLICATION by
transducer
selecting the pressure transducer or level control device as start/stop
(+ 4-20mA -)
device. In the COMBINED application type, it can be selected whether
the pump to controlled by the pressure transducer is either pump 1 or
pump 2.
This input uses 2 or 3 contacts, depending on the selection made as
protection device in menu 5. TYPE OF APPLICATION.
In the COMBINED application type, this entry will only have effect as a
safety device for stopping the pump 1.
In the other types of application, the device connected to this input will
act as I stop the whole system.
Input 1
In all types of application, for the configuration of this input we will
have of the following options: FLOAT SWITCH, MINIMUM PRESSURE
SWITCH, WELL PROBES and NO PROTECTION.
The NO PROTECTION option should be selected if you do not want any
device to can stop the pump(s). Only in case of selecting 3 well probes,
the 3 contacts will be required, in all other cases the connection mar-
ked as an open contact will be used.
This input uses 2 or 3 contacts, depending on the selection made as
start/stop device in menu 5. TYPE OF APPLICATION.
In the COMBINED application type, this entry will only have effect as a
start/stop device for pump 1.
Input 2
In the other types of application, the device connected to this input
will act as start/stop of the pump that you need to start/stop first, in
all other cases the connection marked as an open contact will be used
.
Motor (OUT MOTOR 1 & 2)
220-240V Single Phase (U1 + W2)
220-240V Three Phase (U1 + V1 + W1)
380-420V Three Phase (U1 + V1 + W1)
continues...