12. CONFIGURATION MENU
1. Change the
language
2. Date and time
setting
3. Number of
pumps*
4. Motor
consuption
5. Type of
application
Waste Water
Device
Device
Start/Stop
Protection
Level
Level
Switch
Switch
Device
4-20mA
Programming
Schedule
42
Allows you to choose the language of the device for the settings menu
and for the information that the user will receive on the screen.
Setting for the current time and date, required for time programming
and fault logging.
*(Menu option only available on 2-pump device).
It allows you to select the number of pumps that make up the installation,
allowing you to choose between one or two pumps.
In this section we adjust the nominal consumption of the pump motors.
In installations with two pumps we can set a different consumption of
pump 1 compared to pump 2. This parameter is of utmost importance,
since based on this value we will know if the pump is consuming
excessively or if it is dry working, therefore it is a parameter that directly
affects the useful life of the motors, since if it is not correctly configured,
the pump may not be protected.
We can modify the type of application for which the device is intended,
as well as the start/stop devices and the protection devices against dry
working of the pumps. The available options are:
a) Control of pump(s) for Waste Water
b) Control of pump(s) as Booster Set
c) Well pump control
d) Combined pumps control
The combined pumps option (only available on the two-pump device)
allows completely independent start/stop control and dry run protection
for two pumps. These pumps must have the same connection voltage.
Depending on the selection of the Type of Application, the elements
that will intervene in the activation/deactivation of the pumps must
be selected, as well as the safety device that will be used to prevent
the pumps from dry running. The options depending on the type of
application are the following:
Booster Set
Device
Device
Start/Stop
Protection
Pressures
Level
Switch
Switch
Tank
Well
Probes
Probes
Level
Pressures
Switch
switch
Pressure
No protection
Transducer
device
Programming
Schedule
Well Pump
Device
Device
Start/Stop
Protection
Pressures
Level
Switch
Switch
Tank
Well
Probes
Probes
Level
No protection
Switch
device
Pressure
Transducer
Programming
Schedule
Combined Pumps
Device
Device
Start/Stop
Protection
Pressures
Level
Switch
Switch
Tank
Well
Probes
Probes
Level
Pressures
Switch
switch
Pressure
No protection
Transducer
device
Programming
Schedule